Products - Ensapsultated transformers    Products - HR equivalents

External protection

E4817B

EI 48/16,8

External protection

8.0 VA - 70ºC/B

Logo CE

Simple primary

Dual secondary


E4817B

Weight/unit:

310 gr

E4817B

Weight/minibox (Units: 1)

310 gr

E4817B

Weight/bigbox (Units: 36)

11160 gr

HR Ref. Primary Sec. Sec. In

Vo

(In=0)

External protection Fuse
P1 P2 S1 S2 Is1 Is2

Sec. (F)

S1|S2

Prim. (T)

P1

E4817565 230 V - 4.5 V 4.5 V 889.0 mA 889.0 mA 2x(5.8) V 2x(1000.0) mA 63.0 mA
E4817551 230 V - 6.0 V 6.0 V 667.0 mA 667.0 mA 2x(7.8) V 2x(800.0) mA 63.0 mA
E4817553 230 V - 7.5 V 7.5 V 533.0 mA 533.0 mA 2x(9.7) V 2x(630.0) mA 63.0 mA
E4817555 230 V - 9.0 V 9.0 V 444.0 mA 444.0 mA 2x(11.7) V 2x(500.0) mA 63.0 mA
E4817557 230 V - 12.0 V 12.0 V 333.0 mA 333.0 mA 2x(15.6) V 2x(400.0) mA 63.0 mA
E4817559 230 V - 15.0 V 15.0 V 267.0 mA 267.0 mA 2x(19.5) V 2x(315.0) mA 63.0 mA
E4817561 230 V - 18.0 V 18.0 V 222.0 mA 222.0 mA 2x(23.4) V 2x(250.0) mA 63.0 mA
E4817563 230 V - 24.0 V 24.0 V 167.0 mA 167.0 mA 2x(31.2) V 2x(200.0) mA 63.0 mA
E4817B

Technical characteristics:

  • Designed and manufactured according regulations EN61558 EN60590 EN60472 UL506 UL1585
  • Two-chamber coil
  • Vacuum sealed
  • Safety transformer class II / Protection index IP00 (For all models with no load voltage lower than 50V according to EN61558, and to 30V according to UL1585)
  • External protection with fuse (See suggested type at table)
  • Self-extinguishing plastic UL94-VO
  • Epoxy resin class F
  • Isolation: Prim./Sec. = 10 MOhm to 500 Vcc - Sec./Sec. = 2 MOhm to 500 Vcc
  • Dielectric strength Prim. / Sec. = 5 kV / 1min.
  • Secondary voltage tolerances 5%
  • Test at 100% of all electrical parameters in production
  • Reliability tests for production batch (life term)
  • Certificates of production test results (under request)
  • Certifications VDE, UL; others certifications under request: CSA, SEMKO