Products - Ensapsultated transformers Products - HR equivalents
Types and features | Series index | Technical information
|
HR Ref. | Primary | Sec. | Sec. In |
Vo (In=0) |
Sec. Prot. | |||
---|---|---|---|---|---|---|---|---|
P1 | P2 | S1 | S2 | Is1 | Is2 | CC (*) | ||
E2006114 | 115 V | - | 4.5 V | - | 89.0 mA | - | 7.6 V | CC |
E2006100 | 115 V | - | 6.0 V | - | 67.0 mA | - | 10.2 V | CC |
E2006102 | 115 V | - | 7.5 V | - | 53.0 mA | - | 12.7 V | CC |
E2006104 | 115 V | - | 9.0 V | - | 44.0 mA | - | 15.3 V | CC |
E2006106 | 115 V | - | 12.0 V | - | 33.0 mA | - | 20.4 V | CC |
E2006108 | 115 V | - | 15.0 V | - | 27.0 mA | - | 25.5 V | CC |
E2006110 | 115 V | - | 18.0 V | - | 22.0 mA | - | 30.6 V | CC |
E2006112 | 115 V | - | 24.0 V | - | 17.0 mA | - | 40.8 V | CC |
(*) CC means short-circuit proof
Technical characteristics:
- Designed and manufactured according regulations EN61558 EN60590 EN60472 UL506 UL1585
- Two-chamber coil
- Vacuum sealed
- Safety transformer class II / Protection index IP00 (For all models with no load voltage lower than 50V according to EN61558, and to 30V according to UL1585)
- Short-circuit-protected
- Self-extinguishing plastic UL94-VO
- Epoxy resin class F
- Isolation: Prim./Sec. = 10 MOhm to 500 Vcc - Sec./Sec. = 2 MOhm to 500 Vcc
- Dielectric strength Prim. / Sec. = 5 kV / 1min.
- Secondary voltage tolerances 5%
- Test at 100% of all electrical parameters in production
- Reliability tests for production batch (life term)
- Certificates of production test results (under request)
- Certifications VDE, UL; others certifications under request: CSA, SEMKO