Products - Ensapsultated transformers    Products - HR equivalents

External protection

E3814

EI 38/13,6

External protection

3.5 VA - 70ºC/B

Logo CE

Simple primary

Simple secondary


E3814

Weight/unit:

150 gr

E3814

Weight/minibox (Units: 5)

750 gr

E3814

Weight/bigbox (Units: 80)

12000 gr

HR Ref. Primary Sec. Sec. In

Vo

(In=0)

External protection Fuse
P1 P2 S1 S2 Is1 Is2

Sec. (F)

S1

Prim. (T)

P1

E3814164 115 V - 4.5 V - 778.0 mA mA 6.3 V 800.0 mA 63.0 mA
E3814150 115 V - 6.0 V - 583.0 mA mA 8.4 V 630.0 mA 63.0 mA
E3814152 115 V - 7.5 V - 467.0 mA mA 10.5 V 500.0 mA 63.0 mA
E3814154 115 V - 9.0 V - 389.0 mA mA 12.6 V 400.0 mA 63.0 mA
E3814156 115 V - 12.0 V - 292.0 mA mA 16.8 V 315.0 mA 63.0 mA
E3814158 115 V - 15.0 V - 233.0 mA mA 21.0 V 250.0 mA 63.0 mA
E3814160 115 V - 18.0 V - 194.0 mA mA 25.2 V 200.0 mA 63.0 mA
E3814162 115 V - 24.0 V - 146.0 mA mA 33.6 V 160.0 mA 63.0 mA
E3814

Technical characteristics:

  • Designed and manufactured according regulations EN61558 EN60590 EN60472 UL506 UL1585
  • Two-chamber coil
  • Vacuum sealed
  • Safety transformer class II / Protection index IP00 (For all models with no load voltage lower than 50V according to EN61558, and to 30V according to UL1585)
  • External protection with fuse (See suggested type at table)
  • Self-extinguishing plastic UL94-VO
  • Epoxy resin class F
  • Isolation: Prim./Sec. = 10 MOhm to 500 Vcc - Sec./Sec. = 2 MOhm to 500 Vcc
  • Dielectric strength Prim. / Sec. = 5 kV / 1min.
  • Secondary voltage tolerances 5%
  • Test at 100% of all electrical parameters in production
  • Reliability tests for production batch (life term)
  • Certificates of production test results (under request)
  • Certifications VDE, UL; others certifications under request: CSA, SEMKO