Products - Ensapsultated transformers    Products - HR equivalents

External protection

E6021

EI 60/21

External protection

25.0 VA - 40ºC/B

Logo CE

Simple primary

Simple secondary


E6021

Weight/unit:

560 gr

E6021

Weight/minibox (Units: 1)

560 gr

E6021

Weight/bigbox (Units: 18)

10080 gr

HR Ref. Primary Sec. Sec. In

Vo

(In=0)

External protection Fuse
P1 P2 S1 S2 Is1 Is2

Sec. (F)

S1

Prim. (T)

P1

E6021114 115 V - 4.5 V - 5556.0 mA - 5.4 V 6000.0 mA 315.0 mA
E6021100 115 V - 6.0 V - 4167.0 mA - 7.2 V 5000.0 mA 315.0 mA
E6021102 115 V - 7.5 V - 3333.0 mA - 9.0 V 4000.0 mA 315.0 mA
E6021104 115 V - 9.0 V - 2778.0 mA - 10.8 V 3150.0 mA 315.0 mA
E6021106 115 V - 12.0 V - 2083.0 mA - 14.4 V 2500.0 mA 315.0 mA
E6021108 115 V - 15.0 V - 1667.0 mA - 18.0 V 2000.0 mA 315.0 mA
E6021110 115 V - 18.0 V - 1389.0 mA - 21.6 V 1600.0 mA 315.0 mA
E6021112 115 V - 24.0 V - 1042.0 mA - 28.8 V 1250.0 mA 315.0 mA
E6021

Technical characteristics:

  • Designed and manufactured according regulations EN61558 EN60590 EN60472 UL506 UL1585
  • Two-chamber coil
  • Vacuum sealed
  • Safety transformer class II / Protection index IP00 (For all models with no load voltage lower than 50V according to EN61558, and to 30V according to UL1585)
  • External protection with fuse (See suggested type at table)
  • Self-extinguishing plastic UL94-VO
  • Epoxy resin class F
  • Isolation: Prim./Sec. = 10 MOhm to 500 Vcc - Sec./Sec. = 2 MOhm to 500 Vcc
  • Dielectric strength Prim. / Sec. = 5 kV / 1min.
  • Secondary voltage tolerances 5%
  • Test at 100% of all electrical parameters in production
  • Reliability tests for production batch (life term)
  • Certificates of production test results (under request)
  • Certifications VDE, UL; others certifications under request: CSA, SEMKO